Jaguar Heat Pump Unit

JAGUAR HEAT PUMP UNIT

The Test Bench will have only PC modes of operation. All the tests will be carried out sequentially and the Data will be displayed and stored on PC. Lab VIEW based software and Siemens make PLC as an Interface module will be used to control the whole sequence. Option will be given for selection of test. If in different models of AC Tests are different, then that can be done by selecting the type no. (model) of AC

Earth Bond Test

In this test 10Amp AC current will be passed through Earth Path and the resistance of that Path will be measured and displayed on PC Screen. If the resistance is more than the set value (0.1 Ohms). Fail indication will be given & test will be terminated

Solid state source will be used for HV Test and Insulation Test

High Voltage Test with Ramp up / Down facility

In this test 0 to 6kV AC/DC Solid State source will be provided. High voltage (1.5kV) will be connected between live parts and will have metal body of the AC. If the leakage current will be more than the set value Fail Indication will be given & test will be terminated. Facility to set trip current from 1mA to 40mA for AC & 1mA to 10mA through PC

Insulation Test (Megger Test)

In this test 500V DC will be applied across the live parts in OFF condition and metal body of AC and the insulation resistance is measured and displayed on PC Screen. If the resistance is less than the set value 'Fail' indications will be given and test will be terminated

Earth Leakage Current Test

This test will be carried out with Run (Performance) Test. Rated Supply will be given to the AC and Leakage Current of Earth Path is measured and displayed on the PC Screen. If the current is more than the set value. Fail Indication will be given & Test will be terminated. Facility to set current limit 1mA to 15mA on PC. Leakage Current will be added for each device for comparing the limit

Performance (Run Test)

In this test rated voltage will be applied to the AC and current, wattage will be displayed on PC. Testing will be followed by 19/22C, 19/22d, 19/22e, 19/22f, 19/22j, 19/22j points

  • RPM of Fan Motor will be indicated by using optical sensor (Optional)
  • There will be two pressure Transducer to indicate low pressure and High pressure of the compressor
  • Test time of each test will be settable and any test can be skipped if not required. In Auto mode all the tests will be carried out sequentially and if failure is detected next all the tests will be terminated giving Test over signal
  • The separate output will be provided for five valves V1, V2, V3, V4, V5 of charge unit
  • MS Fabricated panel Trolley Type duly powder coated
  • Input Supply : 3 Phase 4 Wire 415V AC 50 Hz 6 max. For Unit under test supply will be given through your solid state source 240V/35A Single Phase
PC Based Automatic Safety and Performance Test Panel for Single Phase Air Conditioner

PC BASED AUTOMATIC SAFETY AND PERFORMANCE TEST PANEL FOR SINGLE PHASE AIR CONDITIONER

The testing set up for Air Conditioner is designed to carry out the tests as per the IS 302-1979. It broadly consists of testing facilities for following tests

Earth Contact Test

The set-up will consist of adjustable current source of 0-30 Amps. with open circuit voltage not exceeding 12 Volt. The set current can be observed on meter by pressing the push button provided. This Current will be allowed to pass in Earth Contact of Air Conditioner & the drop across the Earth path will be monitored and will be displayed on digital meter in terms of Ohms. In case it exceeds the set value (0.1 Ohms in our case) it will indicate the Failure. This setting can be done with the help of pot meter and can be viewed on digital meter by pressing "Press to Set" push button. The timer adjustable from 1 to 5 sec. will be provided to switch Off the Current after set time. The setting value can be re-adjusted to compensate the cable resistance value. The setting also can be seen on display

High Voltage Test

High Voltage Tester with Voltage adjustment from 0 to 1.5 KV with Tripping Current settings of 2,4,5,6,10 mA, selectable with switch, will be provided. Normally the Output Voltage will be adjusted at 1.5 KV. If the Current exceeds set value the output will be disconnected with "Fault" indication. Setting will be possible without making "HT” ON. Separate HT ON & Timer Start Button will be provided. Timer will be settable up-to 1 Min. The Digital Meter will indicate the leakage current. The tripping setting will be done through switch marked with 2, 4, 5, 6, 10 mA.

Insulation Test

Digital Megger (500V DC) with 20 Meg. Ohm. Range for indication. When the insulation resistance detected is less than 2 mega Ohm the "failure" indication will be provided

Leakage Current Test

The circuit is arranged as per the diagram shown in IS 302 - 1979 : clause 13.2 (figure no.5) with earth removed and equipment kept insulated. (The voltage will be present on the body of the equipment). When the 1.06 times rated Voltage (244 V) is applied to the Air Conditioner the Current flow through meter is monitored and displayed on the digital meter and if it exceeds 0.210mA., the "Fail" indication will be given. The test will be carried out by changing the connections automatically. The tripping value for both the cases will be 0.210mA. This value is also settable, with potmeter, between 0 to 1.000mA and displayed on meter by pressing "Press to Set" push button

Performance Test

The Set-up will compr ise of Variable Voltage Source to adjust supply Voltage 1 Phase 0-270 AC 16 Amp maximum

  • Digital Ammeter – 0 to 16.00A AC – 1 No
  • Digital Voltmeter – 0 to 270V AC – 1 No
  • Digital Wattmeter – 0 to 3.00 KW AC – 1 No
  • Digital Frequency Meter – 40Hz to 60Hz will read the frequency of mains supply

Note: Leakage current Test will be carried along with Performance Test

The above-mentioned Tests will be carried out automatically one by one and if the failure is observed the Test will be terminated and can be proceeded with Manual override. In manual mode individual test can be carried out

The total sequence of operation and annunciation carried of with the help of Micro Controller system

Input Supply – Single Phase 230V AC 50 Hz 25A max. with MCB protection for input supply

Note : The panel will be floor mounting type

Datalogging on PC :

PC Datalogging comprises of :

  • PC Either Dell or HP make. OS will be latest Windows license
  • Interface Module between panel to PC – 1 No
  • Lab VIEW based software to collect and store the data from panel
PC Based testing Setup for Optyma Plus (Controller Based) Model

PC BASED TESTING SETUP FOR OPTYMA PLUS(CONTROLLER BASED) MODEL

Comprises of

  • Variable Voltage Source – 3 Phase adjustable between 0 – 550V @4Amp. The voltage and current will be displayed on computer screen through transmitter. The output of the transducer will be given to DAQ which will degitise the signal give it to PC through interface
  • Computer system with 42” Monitor, CPU, Keyboard, Mouse etc
  • DAQ system
    • This will provide interface between electrical signals such as voltage, current etc and pc
    • Digital Inputs and outputs for relay operation and sensor input such as HP, LP switches & SSPR etc
  • Software for sequence of operation, during testing, collecting the data, displayed / storing the test results and generating reports
  • Output will be brought on terminals for connections to panel
  • Protection cover with interlock will be provided for safety
  • The Panel will be built in extruded aluminum profile for elegant look
  • Panel will be on castor wheels for mobility
Automatic Safety Test Panel for 3 Phase Air Conditioner

AUTOMATIC SAFETY TEST PANEL FOR 3 PHASE AIR CONDITIONER

The testing set up for Air Conditioner designed to carry out the tests as per the IS 302-1979. It broadly consists of testing facilities for following tests

  • Earth Contact Tset
  • High Voltage Test
  • Insulation Test
  • Leakage Current Test
  • Performance Test
PC Based Automatic Safety Test Panel for 1 Phase and 3 Phase Condensing Unit

PC BASED AUTOMATIC SAFETY TEST PANEL FOR 1 PHASE AND 3 PHASE CONDENSING UNIT

The testing set up for condensing unit designed to carry out the tests as per the IS 302-1979. It broadly consists of testing facilities for following tests

  • Earth Contact Test
  • High Voltage Test
  • Insulation Test
  • Leakage Current Test
  • Performance Test
Test Setup for air conditioner

TEST SETUP FOR AIR CONDITIONER

The testing set up for domestic electrical appliances is designed to carry out the tests as per the IS 302

It broadly consists of testing facilities for following tests :

  • Earth Contact Resistance Test
  • High Voltage Test
  • Insulation Test

Get in touch with us